Server Room Cooling Costs

In 2009 when Boho One first opened I never found any good information on the cost of cooling online, 5 years later I now have a good idea.

In its simplest form Boho One’s Server Room consists of 17 cabinets and four Air conditioning units. Each Cabinet is sub metered and the Air condition has meter on in the main electrical distribution room. Equipment is on and cooled 247.

Meter readings as of the 26th of August 2014 are;
  • Server room Total : 367946 KWH 
  • Air conditioning Total : 653266 KWH 
By dividing these two values we calculate the Aircon factor as 1.78

Which means for 1 Kilo Watt Hour of computing it take our building 1.78 Kilo Watt Hours to cool it. Therefore in this simple example for every 1 KWH on someones meter they are actually charged for 2.78 KWH.

Lets add complexity

We take monthly meter readings for charging our customers and therefore have a bit of data to work with. Now to make the information a bit more interesting I'll add in the mean temperature of Middlesbrough for the period.

Meter period
Average Temp
Aircon Factor
September
14º
1.63
October
11º
1.73
November
1.07
December
0.93
January
0.91
February
1.10
March
1.07
April
1.32
May
11º
1.65
June
14º
2.36
July
16º
2.14
August
16º
2.35

As you can see come the hot months it is extremely expensive and this last year actually averages out to be 1.5 which is quite a nice figure to tell people.

We have to charge on a month by month basis as we cycle through tenant in a similar month to month cycle. Unfortunately this is not convenient for tenants who use a similar amount of electricity each month, they have their electric charge more then double in summer .


Just looking at the graph you can see that outside temperature is not the only factors

Other factors

  • During average loads two of the four air conditioning units can manage the temperature. We have no way of tracking  he number of units are active in a period or those in fault.
  • The server room windows face east and can catch the morning sun. Although sunlight is rare in the North of England it could randomly add a degree or two to the server room mean temperature.
Raw data spreadsheet Numbers Format or Excel Format
Weather data from Accu Weather http://www.accuweather.com

2 comments:

Charles Crookes said...

Server rooms are very heated rooms that the heat of the servers and the machines are make it more heated. Costing of the cooling to this room need essay writing service uk reviews by the huge server companies to make their servers be cool.

PDF Editor | A1Office said...

Looking for a versatile PDF editor that can handle everything? Don't look elsewhere—use A1 pdf Editor! This programme is brimming with tools that make modifying PDFs simple. A1 pdf Editor has you covered whether you need to make straightforward or intricate alterations. Additionally, even beginners may easily utilise it because to the simple UI. Why then wait? Take a look at A1 pdf Editor for yourself by downloading it right now.